BKH Series Modular UPS

BKH Brief

BKH series modularized UPS maintains the technical features of traditional tower-type UPS and adopts modularized design to meet the need of modern service room, while ensuring the high reliability of the system. BKH series offers various power modules and cabinet systems, and the user can able to flexibly combine them according to load demand. The capacity of a single cabinet is 200KVA and that of combined cabinets reaches 400KVA.

BKH Main Features

UPS system is modular design, N+X redundancy, hot plugging for system update or capacity expansion
Strong load adaptability and loading capacity, and excellent power grid applicability
Green and energy-saving power supply; overall efficiency>95%, input power factor> 0.99, input current harmonics (THDi)<3%
Dual DSP for independent control of power module, no single point of failure
Digital control of rectification, inverter, charging and discharging via DSP
Integrated and packaged IGBT instead of discrete device to greatly enhance the reliability of power module and UPS system
Front panel for easy maintenance, inlet wire from top to bottom for easy connection by user
Large touch screen of human-machine interface, a great amount of information
Independent charging system, strong charging capacity, Perfect battery management scheme
Parallel connection technology of digital modules, precision circular current index
Easy to install even close to other equipments, space-saving footprint in service room
Redundancy and intelligent adjustable-speed fan, low noise, low power consumption
Integrated distribution system inside system cabinet, easy to install, low investment by user
Good matching performance with motor
DC Starting via battery (cold boot) for easy operation
Three-proofing treatment of all circuit boards.
Optional Standard battery bank or extension battery bank

Capacity (KVA) 1-200KVA
Main Input
Phase   
Input Voltage 380V/400V/415V
Input Frequency 50/60Hz
Power Factor >0.99
Input Total Harmonic Distortion THDi<3%
Input voltage Range -40%~+C1125%
Frequency Range 40-70Hz
Battery
Battery Voltage ±240VDC or ±384VDC
Charger Power 20% * System Power
Charger Voltage Precision 1%
Bypass
Bypass Voltage 380V/400V/415V
Bypass Voltage Range -50%~+20%
Overload Capability 150%1mins, >180%, work time< 100ms
Output
Output Voltage 380V/400V/415V
Output Voltage Regulated Accuracy ±1%( Stable load ), ±3%( fluctuant load )
Total Harmonic Distortion THD<1% ( Linear Load ), THD< 3% ( Non-Linear Load )
Output Power Factor 0.8
Crest Factor 3:01
Overload Capability 125%, switch to bypass after 10H, 150%, switch to bypass after 1H, >150%, switch to bypass after 200ms
System Parameters
System Efficiency Normal Mode: 95%, ECO Mode: 99%
Battery Mode Efficiency 95%
Display LCD+LED, Touch Screen+Keyboard
Protection Level IP20
Communication Port RS232, RS485, Dry contacts, SNMP card, EPO, Generator port
Connection method Support connection of up and down
Running temperature 0-40ºC
Storage temperature -25ºC-70ºC
Relative humidity 0-95% ( no condensing )
Noise (dB) <55dB
Weight (Kg) 6-module cabinet Model: BKH060K/10, BKH090/15, BKH120/20 150Kg
10-module cabinet Model: BKH100K/10, BKH150/15, BKH200/20 180KG
Model: PM10 10kVA power module: 20Kg
Model: PM15 15kVA power module: 21Kg
Model: PM20 20kVA power module: 22Kg
Size ( W*D*H ) mm 6-module cabinet 600*900*1600
10-module cabinet 600*900*2000
Powe module 440*600*134 ( 10KVA/15KVA/20KVA )